The field proven Tactical Power® UPS line is ideally suited for military, industrial, commercial and telecommunications applications that require a high-quality, high-reliability power source that is rugged in construction yet lightweight, compact and mobile. These units are equally suited for use in the field or aboard vehicles, marine vessels, or aircraft in both controlled or hostile environments. The ETI0019-2120EJ is specifically designed for global deployment while delivering up to 2000 VA / 1500 Watts of uninterruptible computer-grade power to critical loads such as computers, .
This UPS is built into a heavy-duty case the size of airline carry-on luggage and includes a popup handle and wheels. When the case cover is closed, the unit becomes watertight. The rounded corners and rugged handles aid in safe handling. Internally, all major components are well secured and electrically insulated to prevent damage due to mechanical shock and vibration. As a portable UPS, the unit can be used in either a horizontal or vertical position.
Designed for both domestic (CONUS) and international (OCONUS) input voltages, this unit's autoranging input voltage selection accepts any AC voltage from 90 to 264 VAC (i.e. nominal 100, 115, 120, 200, 220, 230 or 240 VAC sources) and any frequency from 47 to 63 (i.e. nominal 50 or 60 Hz sources) without special cables or having to open the UPS enclosure. Alternately, the unit also accepts vehicular or aircraft power from nominal 48 VDC systems. This allows the unit to be operated when no AC source is available. Optional 12 VDC and 48 VDC versions are also available.
The high-reliability LED arrays keep the operator informed as to the unit's status including load and battery levels. The high intensity audible alarm can be heard in high noise environments. For situations requiring more stealth, the LEDs can be dimmed or extinguished and the audible feature disabled. All controls and protective devices are brought to front panel with critical controls having finger guards to prevent damage or accidental operation.
The ETI0019-2120EJ has the added benefit of having a field replaceable battery via front drawout battery module. Even if this battery module removed or depleted, this UPS can continue to operate as an electronic power conditioner and frequency converter, providing clean, well regulated, sinusoidal power to the load. The VRLA AGM batteries are maintenance free with immobilized electrolyte and are constructed of flame retardant materials for added safety. For more information, see the Battery Technology section.
A removable and washable intake air filter and high capacity stainless steel ball bearing fans provide added protection in both controlled and hostile environments.
Maintaining documentation for equipment in the field has always been an issue. Instead of having to carry bulky paper documentation, the ETI0019-2120EJ incorporates the eDocs Port™, a patented feature unique to Energy Technologies, Inc. This flash drive contains all the relevant documentation for the unit at hand. This includes Operation and Maintenance manuals as well as training and troubleshooting guides. Utilizing a standard USB interface, these standardized electronic documents are readily available to the user.
Overall, the Tactical Power line is uniquely qualified for critical vehicle, airborne, shipboard, or land based systems combining advanced modular design features with highly reliable construction.
| AC OUTPUT | |
| Output voltage (standard): | 120 VAC true sinewave output standard |
| Output voltage (optional): | 230 or 240 VAC optional settings available and 100, 110 or 120 VAC version available, see ETI0019-2120EE |
| Output rating (standard): | 2000 VA, 1500 Watts standard |
| Output rating (optional): | 1000 VA, 700 watts version available, see ETI0019-2110EF |
| Non-linear load capacity: | Up to 100% non-linear load capability w/o derating |
| Output voltage regulation: | ± 3.0% static regulation of nominal ± 4.0% dynamic (0 to 50% load step) |
| Overload surge capacity: | 110% for 10 minutes; 125% for 30 seconds ± 1.0% w/ utility not available |
| Operational status: | AC Input status, UPS operational, UPS alarm, Battery level, Low battery, Load level, Overload, Hot temperature, +90 dB audible alarm w/audible on/off switch |
| AC INPUT | |
| Input voltage (AC Input): | Autoranging AC Input from nominal 85 VAC to 270 VAC DC Input 21-30VDC |
| Input frequency: | From 45 Hz to 70 Hz standard, optional up to 440 Hz |
| Input power factor: | Better than 99% typically |
| Input/output isolation: | up to 120 dB common mode, <2.0 ma leakage |
| Input transient suppression: | Complies with IEEE 587, UL 1449 and Mil Std 1399 |
| Input power connections: | AC Input One IEC320 male, 3 pin/ DC Input NATO Connector |
| INTERNAL BATTERY | |
| Internal battery type: | Maintenance free immobilized electrolyte, Flame retardant materials (Oxygen Index 28+) |
| Internal battery life: | Rated for continuous service life of 5 years |
| Internal battery protection: | Recessed 100 G shock rated circuit breaker (CB2) |
| Internal battery time: | 3 minutes @ full load |
| Internal battery recharge: | Recharged to nominal in <8 hours |
| Internal battery replacement: | Field Replaceable
<10 minutes to change battery module |
| Battery expansion: | Up to 24 hours w/ optional Battery Expansion Modules |
| DISTRIBUTION PANEL | |
| Output circuits: | Four AC outputs standard, several optional configurations |
| Output receptacles: AC output | NEMA 5-15R with various options |
| MECHANICAL | |
| Dimensions (H x D x W): | 21.75 x 8.99 x 13.75 in (552 x 228 x 349 mm) |
| Unit weight: UPS and Battery |
58 lb. (26 kg) with lift handles front and rear |
| Audible noise: | Less than 47 dB @ 5.0 ft., ANSI "A" scale |
| Cooling type: | High capacity, positive pressure, forced air |
| Air intake filter: | Washable filter media, others optional |
| ENVIRONMENTAL | |
| Storage temperature: | -40° to 158° F ambient (-40° to 70° C) |
| Operating temperature: | 32° to 126° F ambient ( 0° to 52° C), lower/ higher optional |
| Operating humidity: | 0 to 95% relative humidity (non-condensing) |
| Storage elevation: | Up to 50,000 ft (15,240 m), higher optional |
| Operating elevation: | Up to 10,000 ft (3,048 m), higher optional |
| STANDARDS | |
| United States: | Meets UL-1778 standard for UPS equipment, Meets MIL-STDs 1275, 167-1, 454, 810, 1399-300A & MIL-S-901 |
| Canada: | Meets CSA C22.2 No. 107 UPS safety requirements |
| EMI Protection: | Meets EMI/RFI FCC Part 15, Class A; EN55022 |
| OPTIONAL ACCESSORIES | |
| Cold Start, Alternate I/O Configurations, Battery Expansion, Battery Charger/Conditioner, Power Distribution Units |
|